When a shell & tube exchanger starts losing efficiency, the first evidence is almost always in its pressure and flow data — not in the product outlet. Below are the questions our engineering team receives most often from plant operators, with the answers we usually give on site.
Q1. Why does the pressure drop keep increasing?
Because the fluid meets more resistance on its way through the exchanger, so the pump or fan has to work harder to push the same volume through the unit. Energy consumption climbs while the heat actually transferred stays flat or falls. Three conditions are responsible in most cases:
Fouling — scale, sludge, polymer or biological deposits narrow the flow area and insulate the tube wall
Blockage — debris, loose gaskets or failed internals partially obstruct tubes or shell-side passages
Flow path deformation — tube sagging, baffle damage or plate deformation changes the designed channel geometry
Practical trigger point: a pressure drop increase of more than 20–25% against the clean commissioning baseline deserves an inspection — it is not a normal seasonal fluctuation.
Q2. Why do we have to reduce the flow rate to keep the outlet temperature?
Because the exchanger is no longer transferring the heat it was designed for. Operators throttle the flow until the outlet temperature returns to set point, which restores the reading but hides the fault: the effective heat transfer coefficient has already degraded. The plant then runs below rated capacity and pays for the shortfall in output, not only in energy. If a unit needs a lower flow rate to hold the same outlet temperature, treat it as a capacity problem rather than a control tuning issue.
Shell & tube heat exchanger equipment at our manufacturing base in China
Q3. What causes bypass flow inside a heat exchanger?
Part of the fluid short-circuits and leaves the unit without passing over the effective heat transfer surface, so the exchanger behaves like a smaller one. Typical causes:
Leaking or displaced baffles and bypass seals
Internal leakage between shell side and tube side through failed tubes or tube-to-tubesheet joints
Damaged or missing gaskets, or warped plates, on plate-and-frame units
Incorrect nozzle orientation, or bypass lines left open in service
Bypass is easy to miss because total flow and total pressure drop can both look almost normal while outlet temperatures drift apart.
Q4. How do I tell these three faults apart?
What You Observe
Most Likely Cause
Check To Run
Usual Action
Pressure drop rising, outlet temperature falling
Fouling or partial blockage
Compare with clean baseline; inspect tube ends and shell side
Chemical or mechanical cleaning; review strainers
Flow throttled to hold outlet temperature
Loss of heat transfer coefficient
Energy balance and U-value calculation
Cleaning, retubing or capacity re-rating
Outlet temperatures diverging at normal total flow
Bypass, baffle leakage or tube leakage
Pressure test between passes; borescope inspection
Replace gaskets and seals; plug or retube failed tubes
Pump or fan power rising at constant duty
Higher resistance in the flow path
Pump curve vs. measured head; vibration survey
Inspect internals; repair deformation
Q5. Which readings should be trended weekly?
Log pressure drop, flow rate and inlet/outlet temperatures at a fixed reference condition — same load, same ambient, same valve positions. When two of the symptoms above appear together, schedule the inspection before the next production campaign instead of waiting for a forced shutdown.
Heat exchanger units in the production workshop before final inspection
Q6. When is cleaning not enough?
If the unit is repeatedly fouled, or the required duty has grown since commissioning, cleaning only buys time. A correctly specified replacement shell & tube exchanger is often more economical than a cleaning cycle every few months. Send us flow rate, inlet and outlet temperatures, allowable pressure drop and fluid properties — our engineers will size the replacement and confirm the packing and shipping plan to your port.