JIS H3300 C1220T Phosphorus Deoxidized Copper Seamless Tube for Shell and Tube Heat Exchanger and HVAC Systems
Application & Compliance
The JIS H3300 C1220T phosphorus-deoxidized copper seamless tube is specified for HVAC refrigerant circuits, shell and tube heat exchangers, condensers, and evaporators where high thermal conductivity, reliable brazing, and formability are required simultaneously. In HVAC systems, the tube carries refrigerant through evaporator and condenser coils, where the copper matrix delivers the heat transfer efficiency needed to meet equipment capacity ratings without increasing coil size. In shell and tube heat exchangers operating on clean freshwater or steam-condensate duty.
The tube is manufactured and tested in accordance with JIS H3300, the Japanese Industrial Standard for seamless copper and copper alloy tubes. C1220T corresponds to Cu-DHP (Phosphorus-Deoxidized Copper, High Residual Phosphorus) and is equivalent to UNS C12200 under ASTM / ASME specifications, including ASME SB75 and ASTM B75. Certification is available per EN 10204 Type 3.1. Third-party inspection by ABS, GL, DNV, NK, PED, AD2000, and CCS is available upon request.
Problem Solved
HVAC and heat exchanger copper tube failures trace to two primary mechanisms: hydrogen embrittlement during brazing and inadequate formability for U-bend or coil fabrication. Oxygen-bearing copper (C1100) contains copper oxide inclusions that react with hydrogen in reducing brazing atmospheres, generating steam pockets along grain boundaries that cause intercrystalline cracking. C1220T eliminates this risk through phosphorus deoxidation, which removes dissolved oxygen from the melt and leaves a residual phosphorus content that stabilizes the grain boundaries against hydrogen attack during torch or furnace brazing. The result is a brazed joint that remains leak-tight and mechanically sound. For coil and U-bend fabrication, the O temper provides tensile strength ≥205 MPa with elongation ≥40%, allowing tight bend radii without wall thinning or cracking. For straight-length applications requiring higher pressure containment, the 1/2H temper raises tensile strength to the 245–325 MPa range while retaining sufficient ductility for tube-sheet expansion.
Material Specification – JIS H3300 C1220T
C1220T is a phosphorus-deoxidized copper with a minimum copper plus silver content of 99.90% and controlled residual phosphorus. The grade is classified as Cu-DHP and is the standard seamless copper tube material for HVAC, refrigeration, and heat exchanger service in the JIS system.
Chemical Composition (per JIS H3300 C1220T)
| Element |
Requirement |
| Copper + Silver (Cu + Ag) |
≥ 99.90% |
| Phosphorus (P) |
0.015 – 0.040% |
| Total Impurities |
≤ 0.10% |
Chemical composition per JIS H3300 for C1220T. Cu + Ag ≥ 99.90% and P 0.015–0.040% are the defining chemistry limits.
Mechanical Properties by Temper (per JIS H3300 C1220T)
| Temper |
Tensile Strength (MPa) |
Elongation (%) |
Typical Application |
| O (Annealed) |
≥ 205 |
≥ 40 |
Coil, U-bend, severe forming |
| 1/2H |
245 – 325 |
≥ 10 |
Straight lengths, tube-sheet expansion |
| H |
≥ 295 |
≥ 3 |
Strength-critical straight runs |
Thermal and Physical Properties
Thermal conductivity of C1220T is approximately 339 W/(m·K), supporting heat transfer calculations for evaporator and condenser design without relying on oxygen-bearing copper assumptions. The alloy is non-magnetic and retains good ductility at low temperatures, making it suitable for refrigeration circuits. Density is approximately 8.94 g/cm³.
Temper Selection and Formability
The O temper is supplied for coil, pancake, and U-bend fabrication where maximum elongation (≥40%) is required for tight bend radii without cracking. The 1/2H temper provides a balanced combination of strength (245–325 MPa) and limited formability (≥10% elongation) for straight tube lengths that will be rolled or expanded into a heat exchanger tubesheet. The H temper (≥295 MPa tensile, ≥3% elongation) is specified for straight runs where pressure containment and resistance to deformation are the governing requirements rather than post-forming operations. Fabricators should specify temper in the purchase order; the manufacturer’s default shall not be assumed.
Manufacturing Process
Seamless C1220T tube is produced by extrusion, cold drawing, and annealing to the specified temper. The phosphorus deoxidation is performed during melting to ensure uniform distribution of residual phosphorus throughout the tube wall. After final drawing, the tube is annealed in a controlled-atmosphere furnace to the O condition or partially cold-worked to the 1/2H or H temper. Finished tube is eddy-current tested, hydrostatically tested, dimensionally inspected, and cleaned. Tubes can be supplied in straight lengths, pancake coils, level-wound coils, or U-bend form depending on the application.
Testing and Quality Control
Each lot is subjected to the following examinations and tests in accordance with JIS H3300:
-
Chemical Composition Analysis – Verification of Cu + Ag ≥ 99.90% and P 0.015–0.040%.
-
Tension Test – Determination of tensile strength and elongation for the specified temper.
-
Eddy Current Testing (ET) – Non-destructive examination for surface and subsurface discontinuities.
-
Hydrostatic Test – Pressure integrity verification.
-
Dimensional Inspection – Verification of outside diameter, wall thickness, length, and straightness.
-
Surface Inspection – Examination for harmful defects, scale, and cleanliness.
-
Brazing Suitability Verification – Hydrogen embrittlement resistance is inherent to the phosphorus-deoxidized chemistry and confirmed by material certification.
Documentation
Each shipment is supplied with Mill Test Certificates (EN 10204 Type 3.1) covering chemical composition and mechanical properties for the ordered temper, dimensional inspection reports, eddy current and hydrostatic test reports, and material traceability records. Third-party inspection (e.g., SGS, BV, TÜV, DNV, LR, ABS) is available upon request.
For a rapid quotation on JIS H3300 C1220T Phosphorus Deoxidized Copper Seamless Tube, please provide the following information:
-
Quantity (number of pieces, total meters, or weight)
-
Outside diameter and wall thickness
-
Temper (O / 1/2H / H)
-
Length required (straight, coil, or U-bend)
-
Bend radius and leg length (for U-bend tubes)
-
Surface condition requirement
-
Delivery period required