Latest company news about Shell and Tube Heat Exchanger K Values: Complete Data Tables for Coolers, Heaters, Evaporators and Condensers

November 18, 2026

Shell and Tube Heat Exchanger K Values: Complete Data Tables for Coolers, Heaters, Evaporators and Condensers

News Details
Overview

Shell and tube heat exchangers are the workhorses of the process industry. Selecting the correct overall heat transfer coefficient (K value) during the initial design phase is critical. An inaccurate K value leads to insufficient surface area or poor temperature control. At Yuhong Group, we supply premium seamless steel pipes, alloy tubes, and heat exchanger tubes that meet strict dimensional tolerances, ensuring your shell and tube bundles achieve the designed thermal performance.

1. Shell and Tube Coolers
Hot Fluid Cold Fluid K Value [W/(m²·K)] Remarks
Water Water 1395~2836

Fouling factor 5.16×10⁻⁴ m²·K/W

Methanol, Ammonia Water 1395~2836


Organic solvents (<0.5cP)① Water 430~848


Organic solvents (<0.5cP)① Brine 221~569


Organic solvents (0.5~1.0cP)② Water 279~709


Organic solvents (>1.0cP)③ Water 28~430


Gas Water 12~279


Water Brine 569~1162


Water Brine 232~581 Plastic-lined surface
Sulfuric Acid Water 872 Graphite surface; both film coefficients 2441 W/(m²·K)
Carbon Tetrachloride Calcium Chloride Solution 76 Tube-side velocity 0.0052~0.011 m/s
HCl gas (cooling/dewatering) Brine 35~174 Graphite surface
Chlorine gas (cooling/dewatering) Water 35~174 Graphite surface
Roasted SO₂ gas Water 232~464 Graphite surface
Nitrogen Water 66 Calculated value
Water Water 407~1162 Plastic-lined surface
20%~40% Sulfuric Acid Water (30~60°C) 464~1046 Cooling washing sulfuric acid
20% Hydrochloric Acid Water (25~110°C) 581~1162
Organic solvents Brine 174~511

① Benzene, toluene, acetone, ethanol, butanone, gasoline, light kerosene, naphtha, etc.
② Kerosene, hot diesel, hot absorption oil, crude oil fractions, etc.
③ Cold diesel, fuel oil, crude oil, tar, asphalt, etc.
Note: 1cP=1×10⁻³Pa·s.

2. Shell and Tube Heat Exchangers
Hot Fluid Cold Fluid K Value [W/(m²·K)] Remarks
Water Water 1395~2836
Aqueous solution Aqueous solution 1395~2836
Organic solvents (<0.5cP)① Organic solvents (<0.5cP)① 221~430
Organic solvents (0.5~1.0cP)② Organic solvents (0.5~1.0cP)② 116~337
Organic solvents (>1.0cP)③ Organic solvents (>1.0cP) 58~221
Organic solvents (<1.0cP)③ Organic solvents (<0.5cP)① 174~337
Organic solvents (<0.5cP)① Organic solvents (>1.0cP)③ 58~221
20% HCl 35% HCl 581~930 Graphite surface, 35% HCl inlet 20°C, outlet 60°C
Organic solvents Organic solvents 116~349
Organic solvents Light oil 116~395
Crude oil Gas oil 453~510 Tube crude oil velocity 3.05m/s, shell gas oil velocity 1.83m/s
Heavy oil Heavy oil 46~279
SO₃ gas SO₂ gas 6~8

① Benzene, toluene, acetone, ethanol, butanone, gasoline, light kerosene, naphtha, etc.
② Kerosene, hot diesel, hot absorption oil, crude oil fractions, etc.
③ Cold diesel, fuel oil, crude oil, tar, asphalt, etc.
Note: 1cP=1×10⁻³Pa·s.

3. Shell and Tube Heaters
Hot Fluid Cold Fluid K Value [W/(m²·K)] Remarks
Steam Water 1162~3951 Fouling factor 1.72×10⁻⁴ m²·K/W
Steam Methanol, Ammonia 1162~3951 Fouling factor 1.72×10⁻⁴ m²·K/W
Steam Aqueous solution (<2cP) 1162~3951
Steam Aqueous solution (>2cP) 569~2789 Fouling factor 1.72×10⁻⁴ m²·K/W
Steam Organic solvents (<0.5cP)① 569~1162
Steam Organic solvents (0.5~1.0cP)② 279~569
Steam Organic solvents (>1cP)③ 34~337
Steam Gas 28~279
Steam Water 2266~4533 Water velocity 1.2~1.5m/s
Steam HCl or H₂SO₄ 349~581 Plastic-lined surface
Steam Saturated Brine 697~1511 Graphite surface
Steam Copper Sulfate Solution 930~1511 Graphite surface
Steam Air 51 Air velocity 3m/s
Steam (or Hot Water) Non-condensable gas 23~29 Graphite surface, gas velocity 4.5~7.5m/s
Steam Non-condensable gas 35~46 Graphite surface, gas velocity 9.0~12.0m/s
Water Water 407~1162
Hot Water Hydrocarbons 232~500 Water outside tube
Warm Water Dilute H₂SO₄ 581~1162 Graphite surface
Molten Salt Oil 290~453
Heat Transfer Oil Vapor Heavy oil 46~349
Heat Transfer Oil Vapor Gas 23~232

① Benzene, toluene, acetone, ethanol, butanone, gasoline, light kerosene, naphtha, etc.
② Kerosene, hot diesel, hot absorption oil, crude oil fractions, etc.
③ Cold diesel, fuel oil, crude oil, tar, asphalt, etc.
Note: 1cP=1×10⁻³Pa·s.

4. Shell and Tube Evaporators
Hot Fluid Cold Fluid K Value [W/(m²·K)] Remarks
Steam Liquid 1743~4649 Forced circulation, tube velocity 1.5~3.5m/s
Steam Liquid 1162 Horizontal tube
Steam Liquid 1162
Steam Liquid 1395 Vertical short tube
Steam Liquid 2906 Vertical long tube (rising), viscosity <10cP
Steam Liquid 1162 Vertical long tube (falling), viscosity <100cP
Steam Liquid 4649 Forced circulation 2~6m/s
Steam Liquid 2906 Forced circulation 0.8~1.2m/s
Steam Liquid 407~814 Vertical central circulation tube type
Steam Concentrated crystals (salt, sodium dichromate) 1162~3487 Standard evaporative crystallizer
Steam Concentrated crystals (salt, Glauber's salt in caustic soda) 1162~3487 External heating type evaporative crystallizer
Steam Concentrated crystals (ammonium sulfate, gypsum) 1162~3487 Growth-type evaporative crystallizer
Steam Water 2266~4649 Vertical tube
Steam Water 1976~4254
Steam Water 1162~2906 Graphite surface
Steam Caustic Soda 697~755 Horizontal external heating chamber (30~50m²)
Steam 20% HCl 1743~3487 Graphite surface, HCl temp 110~130°C
Steam 21% HCl 1743~2906 Graphite surface, natural circulation
Steam Metal Chloride 930~1743 Graphite surface, metal chloride temp 90~130°C
Steam Copper Sulfate Solution 814~1395 Graphite surface
Water Refrigerant 430~848
Organic Solvent Refrigerant 174~569
Steam Light Oil 349~1023
Steam Heavy Oil (under vacuum) 139~430
5. Shell and Tube Condensers
Hot Fluid Cold Fluid K Value [W/(m²·K)] Remarks
Organic vapor Water 232~930 Plastic-lined surface
Organic vapor Water 291~1162 Graphite surface
Saturated organic vapor (atmospheric) Brine 569~1139
Saturated organic vapor (vacuum with non-condensables) Brine 279~569
Low boiling point hydrocarbons (atmospheric) Water 453~1139
High boiling point hydrocarbons (vacuum) Water 58~1741
21% HCl vapor Water 116~1743 Graphite surface
Ammonia vapor Water 872~2324 Water velocity 1~1.5m/s
Organic solvent vapor and water vapor mixture Water 349~1162 Plastic-lined surface
Organic vapor (vacuum with large non-condensables) Water 58~279
Organic vapor (atmospheric with large non-condensables) Brine 116~453
Freon vapor Water 872~988 Water velocity 1.2m/s
Gasoline vapor Water 523 Water velocity 1.5m/s
Gasoline vapor Crude oil 116~174 Crude oil velocity 0.6m/s
Kerosene vapor Water 2906 Water velocity 1m/s
Steam (pressurized) Water 1987~4254
Steam (under vacuum) Water 1697~3405
Chloroacetaldehyde (outside tube) Water 165 Vertical, borosilicate glass
Methanol (inside tube) Water 639 Vertical
Carbon Tetrachloride (inside tube) Water 363 Vertical
Furfural (inside tube) Water 461 Vertical
Furfural (outside tube, non-condensables) Water 191 Vertical; non-condensable gas present
Steam (outside tube) Water 610 Horizontal
Yuhong Group Supply & CTA

Ensure your shell and tube exchanger performs as designed. At Yuhong Group, we manufacture seamless steel pipes, stainless U-tubes, and finned tubes with precise tolerances. We offer a flexible MOQ (1 Ton), competitive FOB pricing, and a reliable Lead Time (15-25 days). Contact our technical team today for material consultation and a fast quotation.

Frequently Asked Questions
What K value applies to a water-to-water shell and tube cooler?

Typically 1395 to 2836 W/(m²·K) with a fouling factor of 5.16×10⁻⁴ m²·K/W. The value depends strongly on water velocity, tube cleaning condition and the allowable pressure drop.

How high can the K value be in a steam shell and tube heater?

From 1162 to 3951 W/(m²·K) as a general range; with a tube-side water velocity of 1.2 to 1.5 m/s the table gives 2266 to 4533 W/(m²·K).

Why is the K value so low when a gas is involved?

The gas film controls the duty. Cooling a gas with water typically gives 12 to 279 W/(m²·K), and heating a non-condensable gas with steam only 23 to 46 W/(m²·K).